CD Skripsi
Perhitungan Parameter Yang Mempengaruhi Indeks Saifi Dan Saidi Pada Feeder Panam
ABSTRACT
The reliability of the distribution system is a key factor in ensuring a stable supply of electricity to customers. A reliable electricity distribution system has the ability to avoid or minimize power outages, and is able to quickly restore power supply in situations of blackouts. In order to measure and analyze the level of reliability of the electricity distribution system, the method commonly used is SAIFI(System Average Interruption Frequency Index) and SAIDI (System Average Interruption Duration Index). This research was conducted using planned blackout data obtained from PLN feeder Panam in January - July 2023 and compared the results of calculating the SAIFI and SAIDI values for field data with the 1985 SPLN standard. From the calculations it is known that the SAIFI value for field data is 0.35 times/year and the SAIDI value is 0.8 hours/year while the standard SPLN value SAIFI 3.2 times/year and SAIDI 21,094 hours/year sofeeder Panam is declared reliable.
Keywords: Distribution System Reliability, SAIFI and SAIDI
Tidak ada salinan data