Desain Arsitektur Teknik Cerdas Hibrid Untuk Identifikasi Dan Klasifikasi Gangguan Di Sistem Distribusi
Indonesia, the electricity network has growth that occurred in the transmissions and distribution line. The two types of line have an important role in channeling electricity to consumers, so the protection system is needed to protect the load flow from disruption. PT. Chevron Pacific Indonesia (CPI) which is engaged in petroleum exploration, is in desperate need of electricity with a realitively high level of reliability. Fault classification can improve the reliability of the power system. It needs quicken repair process and also reduces the possibility of equipment damage. The power distribution line is modeled using ETAP software. Short circuit types that simulated are phase to ground (F-T), phase to phase (F-F), phase to phase to ground (F-F-T), and three-phase (F-F-F). The ANFIS design is constructed using Matlab GUI 2016a version toolbox. Input data for this ANFIS design are short circuit value which is fed by three phases of voltage and current. The testing runs the RMSE value was achieved during the process for each line in Bangko PT. CPI with each membership function of GaussMF and GBellMF are 0.0003192% and 0.00053327% for BKO1, 0.0001321% and 0.000182% for BKO2, 0.00027386% and 0.00026926% for BKO3, and then 0.00019039% and 0.00021065% for BKO4 respectively. Keywords: ANFIS, fault classifier, membership function, power distribution, short circuit faults