Rugi Daya Pada Kabel Transmisi Dari Gardu Induk Koto Panjang Ke Gardu Induk Garuda Sakti Pekanbaru
transmission cable of Koto Panjang to Garuda Sakti Pekanbaru in March 2014.
This research was conducted with an experimental method and its aim was to
analyze the power losses in the transmission cable. Conductors used in the highvoltage
transmission line was ACSR (Aluminium Conductor Steel Reinforced)
which consisted of a mixture of aluminum and steel with a diameter of 28.71 mm.
Results of the transmission line showed that the largest total conductivity obtained
was 43,645,705.993 Watt at 13:00 PM while the lowest total conductivity was
37,313,100.282 Watt at 17:00 PM. Higher magnitude of the transmitted
conductivity resulted in increased power loss with ACSR conductor resistance of
0.049 Ω so that the largest loss occurred at 13:00 PM with 4,435.645 Watt power
loss and the lowest power loss was 3,221.784 Watt at 17:00 PM. Based on the
results obtained above, the percentages of power lost every hour for a month in
March 2014, were between 0.0086% to 0.0102% with the percentage of overall
average power loss was 0.095%.
Keywords : ACSR, Transmission Line, Power Loss