Kaji Eksperimen Sistem Pendingin Adsorpsi Double Bed Adsorber Dengan Silika Gel-Air Sebagai Pasangan Adsorben-Adsorbat
The adsorption cooling system is one of the technologies for air conditioning and refrigeration systems that are energy efficient and environmentally friendly. The double bed adsorption cooling system with silica gel as adsorbent and water as an adsorbate, and the performance of the system were examined experimentally. The adsorption cooling system consists of two u-tube adsorber with finned tube structure, evaporator, condenser, one heater and one cooling, and is equipped with additional measuring instruments and system components. Based on the test data and calculations obtained, the highest COP value of the adsorption cooling system is 0327 at the time of operation 1200 s with a desorption temperature of 80 ° C on Bed 1. The best SCP value at 1200 s with temperature desorption of 85 ° C with a value of 0.043 kW/kg on Bed 2.Keywords: Adsorption, Desorption, Cooling System, Adsorbent-Silica Gel, Two Bed