Pengaruh Heat Dan Mass Recovery Time Terhadap Unjuk Kerja Chiller Sistem Adsorpsi 2 Bed
Adsorption cooling system double bed with silica gel as adsorbent and water as the adsorbate is expected to reduce the use of refrigerant in the vapor compression system that utilizes refrigerant CFC (hlorofluorocarbon) and HCFC (hydrochlorofluorocarbon) that could potentially damage the ozone layer and increase global warming. This study aims to increase the value of the COP and SCP adsorption cooling system double bed by testing. The method used in this research is by means of heat and mass recovery time of the system. Methods of heat and mass recovery time is done to improve the performance of adsorption double bed system-water pair silica gel as adsorbent-adsorbate. Based on test data and calculations are obtained, the lowest temperature of the water coming out of the evaporator is 11.4oC with a change in average highest temperature was 3.6oC. The highest COP value of the adsorption cooling system is equal to 0.53 to the value of SCP 0.209 kW/kg in heat hecovery time of 40 s and a cycle time of 600 s. While on the mass recovery time obtained value of COP 0.56 and SCP 0.32 kW/kg with a mass recovery of 35 s and a cycle time of 600 s.
Keywords: adsorption, heat recovery, mass recovery, cooling system, silica gel